BGA160201 - Circuit breaker, PowerPacT B, 20A, 1 pole, 600Y/347VAC, 18kA, I-Line, thermal magnetic, 80%, A
Description
Specifications
1.68
2.7
8.02
12.68
https://spin.adhq.com/Schneider%20Electric/bda140151/bda140151.spin
Available in 1, 2, 3, and 4 pole for unit mounts
13924292
Industrial Control Panels, Commercial OEM, Electrical Distribution Equipment, Commercial Buildings and Industrial Building Applications
Square Dâ„¢
USA
US
RoHS
Specification Sheet
Owners/User Manual
Full Engineering Drawing
3606481153289
03606481153289
13924292
BREAKER CKT CASE MLD 600Y/347VAC 20A 1 B
Available in 1, 2, 3, and 4 pole for unit mounts
Dual rated AC/DC with 3 levels of breaking capacity
A wide range of accessories, auxiliaries, and lug connections available
Schneider Electric
2.7000
IN
12.6800
IN
1
253.6000
cu-in
1.6800
LB
8.0200
IN
BGA160201 ; 13924292 ; 03606481153289 ; 3606481153289
Square D
Actuator Type
Toggle
Mounting Type
DIN Rail/Threaded
Number Of Poles
1
PHASE
1
Temperature Rating
deg F
-13 To 158
Trip Range
A
400 to 600
Trip Type
Thermal Magnetic
Voltage Rating
V AC
600Y/347
Wire Size
14 to 2/0 AWG Al/Cu
Amperage Rating
A
20
Color
Gray
Connection Type
Line/Load Lug
Dimensions
5.39 in H x 1.06 in W x 4.01 in D
Enclosure Type
NEMA AB4/IP40
Frame
B
Frequency Rating
HZ
50/60
Interrupt Rating
65 kA at 240 VAC, 35 kA at 480 VAC, 18 kA at 600Y/347 VAC