HJL26060 - Circuit breaker, PowerPacT H, 60A, 2 pole, 600VAC, 25kA, lugs, thermal magnetic, 80%
Description
Specifications
3.95
7.2
7.18
8.36
Standard 80% or 100% rating
8134025
Square Dâ„¢
USA
MX
RoHS
Specification Sheet
Owners/User Manual
Technical Bulletin
0785901706625
00785901706625
8134025
BREAKER CKT CASE MLD 600VAC 250VDC J
Standard 80% or 100% rating
Available in Unit mount, I-line or Drawout constructions
A wide range of accessories, auxiliaries, and lug connections available
PowerPact HJL26060 Type HJL Molded Case Circuit Breaker, 600 V AC/250 V DC, 60 A, 20/25/65/100 kA Interrupt, 2 Poles, Thermal Magnetic Trip ; Schneider Electric ; Square D ; HJL26060 ; HJL26060 ; 785901706625 ; Molded Case Circuit Breakers
Schneider Electric
7.2000
IN
8.3600
IN
1
414.7200
cu-in
3.9500
LB
7.1800
IN
HJL26060 ; 8134025 ; 785901706625 ; 78590170662 ; 00785901706625 ; 0785901706625
https://www.youtube.com/embed/4wUOBk4oUmk
Square D
Actuator Type
Toggle Handle
PHASE
1
Temperature Rating
deg C
40
Trip Range
A
60/800/1450
Trip Type
Thermal Magnetic
Type
80% Rated Type HJL
Voltage Rating
600 V AC/250 V DC
Wire Size
AWG
14 to 3/0
Amperage Rating
A
60
Connection Type
Line/Load Lug
Dimensions
4.36 in L x 2.74 in W x 6.4 in H
Frame
J
Frequency Rating
HZ
50/60
Interrupt Rating
250 VDC/600 VAC/65 kA at 480 VAC/25 kA at 600 VAC/100 kA at 240 VAC/20 kA at 250 VDC
Mounting Type
Unit
Number Of Poles
2